Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/12/2012 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 08/28/2012 |
PLUMBING - INTERMEDIATE |
|
Denied |
1. Plumbing out of the wall at the water service and at the T&P relief drain. Relief drain backpitched and not supported. 2. ABS is to be supported at each change of direction or elevation and at the end of branches, then no more than four feet between hangers. Table 3-2 2006 UPC. ABS shims, plumbers tape, unstrapped 2x4s and wall members are not approved methods of support. 3. Continued not readys may result in a reinspection fee. |