Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/27/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 06/20/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/18/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL BUSHINGS AT LB TERMINATIONS AT SERVICE PANELS. 2) FITTINGS MUST BE RATED FOR NEMA 3R. NOT SET SCREW FITTINGS. SUPPORT 3/4" CONDUITS TO WALL 3) STRAP & BURY #4 BARE GROUND 4) RD CIRCUIT BREAKERS 5) STILL HAVE UNSAFE WIRING IN FRONT OF UNIT "A" 6) PROVIDE LADDER FOR ROOF INSPECTION |