Permit: T12CM03316

Parcel: 120073860

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/29/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/27/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
06/20/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/18/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL BUSHINGS AT LB TERMINATIONS AT SERVICE PANELS.
2) FITTINGS MUST BE RATED FOR NEMA 3R. NOT SET SCREW FITTINGS. SUPPORT 3/4" CONDUITS TO WALL
3) STRAP & BURY #4 BARE GROUND
4) RD CIRCUIT BREAKERS
5) STILL HAVE UNSAFE WIRING IN FRONT OF UNIT "A"
6) PROVIDE LADDER FOR ROOF INSPECTION