Permit: T12CM03274

Parcel: 11006097B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/29/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/03/2013 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/03/2013 ELECTRIC - FINAL Not ready for Inspection PROVIDE SMOKE DETECTORS AS REQUIRED & PERMITS FOR NEW A/C & WATER HEATER
12/05/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999
THE GROUNDING ELECTRODE SYSTEM HAS BEEN VANDALIZED. PROVIDE 2-8' GROUND RODS MIN 6' APART & RECONNECT NEW GROUNDING ELECTRODE CONDUCTORS TO SERVICE. CAP OFF ALL OPEN CONDUCTORS INSIDE UNITS IF FIXTURE IS NOT INSTALLED. PROVIDE WATER TO GAS BOND TO ELEC SYSTEM.