Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2013 | FIRE - FINAL | Approved | ||
| 01/28/2013 | FIRE - FINAL | Denied | 2006 IFC 1008.1.8.4 Correct double doors can not use slide bolt locks to lock door on south door. 2006 IFC 1008.1.9 & 10.11.1 Correct 2nd exit door from dinning room need panic hardware and exit sign over door. IFC 1008.2 Gate on patio needs to open with panic hardware or freely open with no locking latch. |