Permit: T12CM03245

Parcel: 121012610


Addresses:

5915 E PIMA ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/17/2012 BUILDING - FINAL Approved IVRS - Inspection :*
12/14/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GROUND RODS ARE TO BE MIN. 6" APART.
PROVIDE ACCESS TO ROOF & INSIDE BUILDING
11/07/2012 BUILDING - FINAL Partial Approval STILL NEED ITEMS 1,2,3 FROM PREVIOUS INSPECTION AND NOTES 2 AND 4 FROM 9/28
10/10/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE RISER AND CONDUCTOR NOT INSTALLED
2) NEED GROUNDING ELECTRODE SYSTEM 250.50 AND 250.58
3) SERVICE NOT LABELLED
4) SECONDARY FEED CONDUCTORS NOT INSTALLED
5) BOND SERVICE PANEL 250.24
6) MAINTAIN WORKING SPACE AT SUB PANEL
7) FINISH #2,3,4,5
10/08/2012 BUILDING - FINAL Partial Approval AIR BALANCE REPORT OK
09/28/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSED CONDUCTORS- MISSING COVER PLATES
2) LIGHTING NOT AS PER PLANS AND FANS
3) BREAKERS NOT DISTINGUISHABLE FROM ONE ANOTHER 408.4 AND PERMANENT DIRECTORY
4) REMOVE MAIN DONDING JUMPER AT SUB PANEL
5) LOOSE CONDUCTOR TERMINATION
6) SERVICE STILL NOT AS PER PLANS, CAN NOT DETERMINE LOCATION OF MAIN
7) STILL NEED AIR BALANCE REPORT
09/27/2012 BUILDING - FINAL Not ready for Inspection CANCELLED
09/20/2012 BUILDING - FINAL Not ready for Inspection ELEC AT THE SERVICE AND AT SUBPANEL NOT REFLECTIVE OF THE APPROVED PLANS, CEILING FAN APPEARS TO BE MISSING SWITCHES AT ENTRY MISSING MOUNT THERMOSTAT TO WALL PROVIE AN BALANCE REPORT FOR OUTSIDE AIR AND AIR SUPPLY