Permit: T12CM03236

Parcel: 130052880


Addresses:

1933 E 34TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/15/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
06/06/2012 ELECTRIC - RECONNECT Denied 1. GROUND SERVICE TO CODE - 2 GROUND RODS 6' MIN APART, BOND WATER, GAS.
2. LABEL SERVICES (ADDRESSES), DEAD FRONT MISSING ON SERVICE PANEL, SUPPORT FLEX CONDUIT, MC CABLE TO STRUCTURE, OPEN SPLICES,(BACK OUTSIDE)
3. SMOKE DETECTORS REQUIRED IN ALL BEDROOMS
4. BEDROOMS & KITCHEN COUNTERS RECEPTACLES SHOULD BE GFI PROTECTED