Date Description Inspector Results Comments
03/19/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/28/2013 ELECTRIC - FINAL Denied -no compliance with last inspection notes
-a resinpection fee will be assessed next inspection if not compliance
09/20/2012 ELECTRIC - FINAL Denied -WIRING TO BE IN RACEWAY CONTINUOUS INTO CONTROL CABINATE
-EQUIP GROUND HAVE GREEN INSULATION CONTINOUS
- PVC EXPOSED TO BE SCH 80 250 300
09/06/2012 ELECTRIC - FINAL Partial Approval -PLEASE RESCH. INSPECTION WHEN CONTR. ON SITE TO OPEN MOTOR CONTROLLERS FOR WIRING CONNECTIONS