Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T12CM03227
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/28/2013 | ELECTRIC - FINAL | Denied | -no compliance with last inspection notes -a resinpection fee will be assessed next inspection if not compliance |
|
| 09/20/2012 | ELECTRIC - FINAL | Denied | -WIRING TO BE IN RACEWAY CONTINUOUS INTO CONTROL CABINATE -EQUIP GROUND HAVE GREEN INSULATION CONTINOUS - PVC EXPOSED TO BE SCH 80 250 300 |
|
| 09/06/2012 | ELECTRIC - FINAL | Partial Approval | -PLEASE RESCH. INSPECTION WHEN CONTR. ON SITE TO OPEN MOTOR CONTROLLERS FOR WIRING CONNECTIONS -PROVIDE ELECTRICAL PLAN |