Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | 1. OLD SERVICE IN HAZARDOUS CONDITION- NITIFYING TEP 2. FILL UNUSED PORTIONS OF OPENINGS IN BACK OF PANEL WITH NON COMBUSTABLE PRODUCT 3. SECURE NM CABLE ENTERING PANEL WITHIN 8" 4. CANNOT RUN SEPERATE NEUTRAL TO SUB PANEL - IS TO BE WITH CONDUCTORS IN SAME WIRING METHOD. 5. CONDUCTOR MARKING TAPE TO ENCIRCLE CONDUCTOR |