Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2012 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 07/31/2012 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | 1) GROUND AND NEUTRAL TO BE ON SEPERATE BARS 2) CONDUIT TO DRYER OUTLET TO BE STRAPPED 3) ALL REAMS BELOW 7' TO BE PROTECTED 4) EXTERIOR LIGHT AT LAUNDRY TO BE IN BOX |