Permit: T12CM03019

Parcel: 134042730


Addresses:

400 S PORTER AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/21/2012 PLUMBING - FINAL Approved IVRS - Inspection :*
08/24/2012 PLUMBING - FINAL Not ready for Inspection PROVIDE DOCUMENTATION ALLOWING CELLULAR CORE ABS
PROVIDE CONDENSATE KIT INSTALL INSTRUCTIONS SPECIFIED ON PG12 #2
DEDICATED OUTLET REQUIRED
08/21/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/08/2012 PLUMBING - FINAL Denied READ AND FOLLOW INSTALLATION INSTRUCTIONS FOR POWER VENTED WATER HEATER. SEE PAGES 10,11,12,AND 16. SOLID CORE ABS OR CELLULAR PVC OR PVC OK.
SOLVENT CEMEMTING DIFFERENT TYPES OF PLASTIC PIPE IN DOORS IS PROHIBITED BY 1PC 605.9. (VERTICAL VENT) HAS BACK PITCH. PROTECT PLASTIC PIPE FROM UV RAYS. INSTALL A ROOF FLASHING. TERMINATE VENT AS SPECIFIED, B VENT CAP MAY NOT BE USED..
08/08/2012 PLUMBING - FINAL Not ready for Inspection PLEASE IMPOSE A REINSPECTION FEE. CONTRACTOR SHALL PAY A REINSPECTION FEE FOR FAILURE TO COMPLY WITH PREVIOUSLY NOTED ITEMS.
08/06/2012 PLUMBING - FINAL Not ready for Inspection B VENT MAY NOT BE USED PER INSTALL INSTRUCTIONS. CORRECT PIPE INSULATION. ALL JOINTS OF PLASTIC SHALL BE PROPERLY INSTALLED
07/26/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/11/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE PROPER VENTING OF GAS WATER HEATER, SEE INSTALLATION BOOKLET FOR BRADFORD WHITE WH
PROTECT PIPE INSULATON FROM HEAT SOURCE.
SUPPORT ALL TUBING
MAKE MIXING VALVE ACCESSIBLE
AIR CAP REQUIRED ON RELIEF DRAIN
PLUG DRAIN PAN - OR PIPE RELIEF DRAIN TO APPROVED RECEPTOR
SEDIMENT TRAP REQ ON GAS SUPPLY
GAS FLEX IS UNDERSIZED FOR 76000 BTU
PIPING MAY NOT BE RESTRICTED IN SIZE
CORRECT PIPE INSULATION