Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T12CM02987
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2012 | PLUMBING - INTERMEDIATE | Approved | ||
| 08/16/2012 | PLUMBING - INTERMEDIATE | Partial Approval | 1. Gas pressure test OK. 2. Insulation not per plan. Provide approval for half inch armaflex. 3. OK to cover walls subject to insulation approval. | |
| 08/14/2012 | PLUMBING - INTERMEDIATE | Partial Approval | 1. ABS is to be supported at each change of direction or elevation, and at the end of branches, then no more than four feet between hangers. Provide mid-story guides for vertical piping. Support all copper piping per Table 3-2 2006 UPC. OK to insulate hot piping per plan- See General Plumbing Notes #6. Water piping incomplete. | |
| 08/06/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |