Permit: T12CM02987

Parcel: 12510052A


Addresses:

3100 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T12CM02987

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/13/2012 PLUMBING - INTERMEDIATE Approved
08/16/2012 PLUMBING - INTERMEDIATE Partial Approval 1. Gas pressure test OK. 2. Insulation not per plan. Provide approval for half inch armaflex. 3. OK to cover walls subject to insulation approval.
08/14/2012 PLUMBING - INTERMEDIATE Partial Approval 1. ABS is to be supported at each change of direction or elevation, and at the end of branches, then no more than four feet between hangers. Provide mid-story guides for vertical piping. Support all copper piping per Table 3-2 2006 UPC. OK to insulate hot piping per plan- See General Plumbing Notes #6. Water piping incomplete.
08/06/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*