Permit: T12CM02957

Parcel: 140232400


Addresses:

5915 S SOUTHLAND BL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/06/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/05/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RISER SUPPORT SHOULD HAVE 1/4" BOLTS TO WALL SUPPORT, #10 SCREWS NOT STRONG ENOUGH
2) HOW DID YOU PENERATE WALL WITH LOAD CONDUCTORS CANNOT SEE BEHIND PLATE.
USE A NON COMBUSTIBLE SEALANT GOING THRU PLYWOOD
NOTE: SERVICE RE-ENERGIZED PRIOR TO INSPECTORS APPROVAL