Permit: T12CM02811

Parcel: 115044910


Addresses:

1020 N TYNDALL AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T12CM02811

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2013 FIRE - FINAL Approved
08/30/2013 FIRE - FINAL Partial Approval 1. FIRE LANES OBSTRUCTED BY VEHICLES AND NOT SURE WHO GAVE THE OKAY TO PUT CONSTRUCTION TRAILER IN THE ROADWAY ON TYNDALL.
2. N. STAIRWAY DOOR AT GARAGE NEEDS PLATE ON DOOR
3. PROVIDE 3 COMPLETE SETS OF KEYS FOR THE KNOX BOXES. LABEL ALL KEYS
4. HANDRAIL AT BOTTOM OF STAIRS APPEARS TO BE NOT SECURE
5. EVACUATION SIGNS IN ELEVATOR LOBBY MAY NEED TO BE PUT ON OPPOSITE WALL FOR BETTER ORIENTATION
6. ROOF/SOUTH EXIT STARWELL NEED PLATE TO COVER DOOR AT HARDWARE
7. PAINTED SPRINKLER HEAD IN MENS'S BATHROOM ON ROOF LEVEL
8. ELEVATOR CONTROL ROOM DOOR WEDGED OPEN
9. OPEN ELECTRICAL JUNCTION BOX AT ROOF LEVEL IN CORRIDOR.
10. STORGE IN SOUTH SIDE CORRIDOR/ROOF LEVEL
11. PENTHOUSE LOBBY- STORAGE OF COMBUSTIBLES
12. ELECTRICAL ROOM PENTHOUSE-DOOR WAS WEDGED OPEN AND WHAT IS THE GATE ALL ABOUT?
13. LOCK ALL FIRE DAMPER/ACCESS DOORS IN HALLWAYS OR ROOMS. SEVERAL THROUGHOUT BUILDING WERE UNLOCKED.
14. GASKETS MISSING ON 13TH FLOOR ELEVATOR LOBBY DOORS.
15. TRASH/STORAGE IN 13TH FLOOR STAIR 1
16. 12TH FLOOR STORAGE/TRASH STORED NEXT TO TRASH CHUTE.
17. 11TH FLO0R ELECTRICAL ROOM BLOCKED OPEN
18. 11TH FLOOR ELEVATOR LOBBY GASKED MISSING
19. 10TH FLOOR STORAGE/TRASH IN CORRIDOR
20. 9TH FLOOR CEILING ACCESS DOOR OPEN.
21. 9TH FLOOR STORAGE IN CORRIDOR
22. 9TH FLOOR ELEVATOR DOORS-MAGNETS FELL OFF. ONLY ON VIA SET SCREW. ALL LOBBY DOORS SHOULD BE CHECKED
23. 8TH FLOOR DOOR TO ACCESS VALVE UNLOCKED IN CORRIDOR WALL
24. 7TH FLOOR TRASH OUTSIDE TRASH CHUTE
25. 6TH FLOOR TRASH STORED IN ELEVATOR LOBBY
26. 5TH FLOOR ELECTRICAL ROOM DOOR BLOCKED OPEN
27. 3RD FLOOR TRASH STORED IN HALLWAY OUTSIDE TRASH CHUTE
28. 2ND FLOOR DOOR UNLOCKED TO VALVES IN CORRIDOR WALL NEXT TO TRASH CHUTE
29. DOUBLE DOORS TO STUDY LOUNGE, RATED? GASKETING NOT IN. HOLES IN SIDE OF DOORS
30. LOADING DOCK DOORS 1ST FLOOR-RATED? DO NOT CLOSE AND LATCH ON THEIR OWN
31. ELECTRICAL ROOM 1ST FLOOR. REMOVE ALL STORAGE AND PROVIDE GASKETING FOR RATED ASSEMBLY
32. BATHROOM NEXT TO BREAKROOM-SPRINKLER HEAD TRIM PLATE MISSING.
08/12/2013 FIRE - FINAL Partial Approval Alright for a 30 temp. I will verify a few exiting items, smoke alarms, and sprinkler heads this week. OVERTIME FIRE INSPECTION FEES NEED TO BE PAID. KRB
07/16/2013 FIRE - FINAL Denied Partial approval given for moving in furniture when Kazal turns on sprinkler system with fire pump on line. NO PUBLIC MOVE IN UNTIL FINAL C of O IS APPROVED THIS MEANS ALL WORK SHALL BE COMPLETED.