Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T12CM02811
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/26/2013 | FIRE SPKLR - FINAL | Approved | ||
07/16/2013 | FIRE SPKLR - FINAL | Partial Approval | Partial approval given for moving in furniture when Kazal turns on sprinkler system with fire pump on line, Tested emergency switch over with fire pump running, emergency generator switched over in 19 seconds fire pump started back up no problems. NO PUBLIC MOVE IN UNTIL FINAL C of O IS APPROVED THIS MEANS ALL WORK SHALL BE COMPLETED. |