Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T12CM02811
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2013 | ELECTRIC - FINAL | Approved | PER BU FINAL | |
08/12/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
08/07/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/06/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
08/06/2013 | ELECTRIC - FINAL | Not ready for Inspection | CORRECTION NOTICE: NEED EXIT LIGHTING ON 2ND FLOOR AT 3 LOCATIONS - SEE PAGE E202 |
|
08/05/2013 | ELECTRIC - FINAL | Partial Approval | EMERGENCY LIGHTING PROGRESS AREA. PROGRESS ON ELECTRICAL ROOMS. WALK WITH FIRE DEPT ON GENERATION SHUT DOWN AND STAIRWELLS | |
08/01/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/31/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/31/2013 | ELECTRIC - FINAL | Partial Approval | 2ND LEVEL HOT CHECK - DORMS ONLY | |
07/30/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/30/2013 | ELECTRIC - FINAL | Partial Approval | HOT CHECK REINSPECT ON LEVEL 5 & 11 NEED ELEC ROOM ON ALL LEVELS MUST BE COMPLETED WITH FIRESTOP |
|
07/29/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/29/2013 | ELECTRIC - FINAL | Partial Approval | PROGRESS AREA HOT CHECK LEVEL 2 & 11 | |
07/27/2013 | ELECTRIC - FINAL | Partial Approval | HOT CHECK ON LEVELS 14, 13, 10, 9.8 OK | |
07/26/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/25/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/25/2013 | ELECTRIC - FINAL | Partial Approval | PROGRESS AREA HOT CHECK - 9-10TH FLOOR | |
07/24/2013 | ELECTRIC - FINAL | Partial Approval | HOT CHECK PROGRESS AREA | |
07/22/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
07/21/2013 | ELECTRIC - FINAL | Partial Approval | HOT CHECKS LEVEL 3-7. PROGRESS AREA | |
07/15/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/13/2013 | ELECTRIC - FINAL | Not ready for Inspection | NEED TO RESOLVE ARC FAULT IN BEDROOMS | |
07/11/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/11/2013 | ELECTRIC - FINAL | Denied | NOT IN COMPLIANCE | |
06/24/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
06/22/2013 | ELECTRIC - FINAL | Partial Approval | SMOKE FIRE DAMPERS ON ALL VERTICAL SHAFT ACCUATES MOVEMENT OK | |
06/19/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |