| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2012 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/22/2012 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER HAMMER ARRESTORS REQUIRED 2) A REDUCER IN THE RUN IS A RESTRICTION AND A CODE VIOLATION (NOT PER PLAN). INSTALL 1" TO FIRST TEE 3) INSULATE OR ISOLATE PEX FROM ROOF 4) SECURE ALL TUBING AS REQUIRED 32" MAX 5) SECURE COPPER CLOSE TO SHUT OFF VALVES 6) REPAIR DAMAGED TOP PLATE AT EXT KIT WALL-USE SIMPSON STRAP WITH 16P NAILS IN EVERY HOLE 7) ALL HOSE BIBS REQUIRE VACUUM BREAKERS 8) REPLACE PB SUPPLY TUBES TO FIXTURES 9) SECURE BLOCK AT CW SUPPLY TO WATER HEATER 10) PROVIDE 6" CLEARANCE BETWEEN DRYER VENT AND PEX |