Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T12CM02770
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/06/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK ROUGH IN SOFFIT- NEED TO VERIFY LTG CONTRACTOR OK BOTTOM ROW STRIP LTG. OUT FRONT. |
|
07/25/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
07/16/2012 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) VERIFY DERATING OF CONDUCTOS PER 310.15 & 310.16 2) CONTACTORS TO BE LISTED NOT RECONIZED COMPONETS 3) CLEAN SURFACE UNDER GROUND BAR 250.12 JUNCTION BOX 4) VERIFY BOX FILL OF SINGLE GAUGE BOX - ROOF EDGE 5) NEED SOFFIT ACCESS PLEASE HAVE ELECTRICIAN PRESENT * NO WORK APPEATRS DONE FOR EXISTING INTERIOR LIGHTING AT THIS TIME |