Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2012 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 09/20/2012 |
MECHANICAL - FINAL |
|
Partial Approval |
SUPPORT DUCT ON ROOF AT CANVAS CONNECTORS . PROVIDE A SUN SHIELD OVER CANVAS CONNECTORS SUPPORT ALL LINE SETS ON ROOF BLDG F |
| 08/02/2012 |
MECHANICAL - FINAL |
|
Partial Approval |
FAN COILS IN SUITE 134- OK |
| 07/31/2012 |
MECHANICAL - FINAL |
|
Partial Approval |
FAN COILS OVERFUSED. WHITE WIRE USED FOR HIGH VOLTAGE CONDUCTOR. EXTEND VENTS ON CONDENSATED DRAINS. PROVIDE BUSHINGS IN FAN COIL KNOCKOUTS. |