Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/27/2012 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/27/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING ELECTRODE CONDUCTOR TO BE BOUNDED PER 250.64 METAL RACEWAYS 2. WHERE IS LIGHT SWITCH FOR LIGHT AT INVERTER + DISCONNECT 3. ALL DISCONNECTION MEAN TO BE LABELED PER 640.17 4. PLEASE OPEN INVERTER FOR INSPECTION 5. BONDING TO BE PER INSTRUCTION FOR SOLOR CITY 690.41 6. SUPPORT LOOSE CONDUCTORS + DC DISCONNECT UP UNDER PANELS 7. NO MORE THAN 360 IN CONDUIT RUNS 8. PROVIDE ACCESS TO REAR ROOF 9. WHERE IS AC SIDE CONNECTION NOT AS PLANS |