Permit: T12CM02618

Parcel: 11941176D


Addresses:

1795 W AJO WY

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/30/2012 PLUMBING - FINAL Approved IVRS - Inspection :*
10/29/2012 PLUMBING - FINAL Partial Approval PVC,ABS VENTING TO BE RECOATED FOR U.V PROTECTION
10/26/2012 PLUMBING - FINAL Not ready for Inspection 1. MC NOT TO TIE TO STRUCTUAL SUPPORT
2. FLUE ON WATER HEATER INSTALLED UP SIDE DOWN, DON'T PUT SCREWS IN DOUBLE WALL PIPE
3. PROVIDE MINIMUM 1/4" PER FOOT ON CONDENSATE
4. PROVIDE MINUMUM 2" BEADED COLLARS ON ALL FLEX DUCT CONNECTIONS