Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/06/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE LISTED RISER CONDUIT BRACE 2. GROUND J-BOX WITH EQUIP, GROUD, NOT NEUTRAL 3. UNIT MUST BE OPEN FOR RECONNECT INSP 4. GFI TO BE UNSPLITED TO GROUND BAR FROM GROND RODS 5. NO NON ELECTRICAL PIPING BELOW PANEL MUST BE CLEAR TO GROUND LEVEL MAY HAVE TO RELOCATE PANEL' 110-26 NEC |