Permit: T12CM02581

Parcel: 137102140


Addresses:

5457 S CANADA DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/14/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/06/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE LISTED RISER CONDUIT BRACE
2. GROUND J-BOX WITH EQUIP, GROUD, NOT NEUTRAL
3. UNIT MUST BE OPEN FOR RECONNECT INSP
4. GFI TO BE UNSPLITED TO GROUND BAR FROM GROND RODS
5. NO NON ELECTRICAL PIPING BELOW PANEL MUST BE CLEAR TO GROUND LEVEL MAY HAVE TO RELOCATE PANEL' 110-26 NEC