Permit: T12CM02580

Parcel: 128020430


Addresses:

6102 E 16TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/27/2012 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
09/25/2012 ELECTRIC - SERVICE UPGRADE Denied 1. #1 FROM PREVIOUS INSPECTION BRACING FOR RISER STILL HAS TO BE CORRECTED.
2. 2-2 HOLE STRAPS 8" APART WITH 1/4 LAGS SCREWS NOT SHEET ROCK SCREWS.
3. 2 GROUND RODS MISSING
09/12/2012 ELECTRIC - SERVICE UPGRADE Not ready for Inspection NO ONE HOME- DOGS IN YARD (1235 HOURS) PLEASE LEAVE A CONTACT PHONE # ON MESSAGE SYSTEM
08/17/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BRACING FOR RISER TO BE 8" FROM WEATHER HEAD
2. 2 WILL NOT ENTER YARD WITHOUT SOMEONE HERE TELLING ME 2 CAN, CALL INSPECTION BACK IN WHEN SOMEON CAN BE HERE
08/15/2012 ELECTRIC - SERVICE UPGRADE Not ready for Inspection KNOCKED NO ONE PRESENT FOR ACESSS AT 9:05 AM
DOG IN YARD RE CALL
08/10/2012 ELECTRIC - SERVICE UPGRADE Denied -RISER BRACE NEEDED
-UNDERSIZED SERVICE ENTRANCE CONDUCTORS
-NOT READY STOPPED INSPECTION