Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/24/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/13/2012 MECHANICAL - FINAL Denied T ADN P DRAIN MUST SLOPE DOWNHILL.
PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTOR.
REPLACE USED GAS FLEX CONNECTOR.
PROVIDE MIN. 1/8" PER FT SLOPE ON CONDENSATED DRAINS AND SUPPORT EVERY 4'
PROVIDE A GFI SERVICE RECEPTACLE ON ROOF
PROVIDE AN APPROVED J BOX. PROVIDE PROPER SIZE CONDUCTORS
06/21/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE GROUNDING ELECTRODE TO STRUCTURE
2. 1ST GROUND CLAMP NOT INSTALLED CORRECTLY
3. OLD PANEL CAN NOT BE USED AS JUNCTION BOX
4. SEAL ENTRANCES ABOVE CURRENT PARTS WITH AN APPROVED DEVICE
5. BREAKER AMPACITYS NOT SIZED TO CONDUCTORS
6. PLEASE PROVIDE ROOF ACCESS
7. SUPPORT CONDUIT TO WALL