Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2012 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/13/2012 | PLUMBING - FINAL | Denied | T ADN P DRAIN MUST SLOPE DOWNHILL. PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTOR. REPLACE USED GAS FLEX CONNECTOR. PROVIDE MIN. 1/8" PER FT SLOPE ON CONDENSATED DRAINS AND SUPPORT EVERY 4' PROVIDE A GFI SERVICE RECEPTACLE ON ROOF PROVIDE AN APPROVED J BOX. PROVIDE PROPER SIZE CONDUCTORS |
|
| 08/10/2012 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |