Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/30/2012 | BUILDING - FINAL | Denied | 1) MAINTAIN WORKING SPACE AT A/C DISCONNECT 2) SEAL ENTRANCESABOVE CURRENT CARRING PARTS 3) GROUNDING TO BE A LISTED SYSTEM 690.41, 690.43 IF USING THE WEED MODULE CAUTIONS YOU NEED TO USE ALL THE PARTS OF THE LISTED SYSTEM 4) PLEASE PROVIDE INSTRUCTIONS FOR RACK MOUNTING AS INSTALLED PLANS SHOW DIFFERENT 5) INSTALL BOND JUMPER ON SERVICE MIPPLE 250.92 *MAIN BREAKER WAS CHANGED WITHOUT CLEARANCE |