Permit: T12CM02501

Parcel: 133124490

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/31/2012 BUILDING - FINAL Approved IVRS - Inspection :*
07/30/2012 BUILDING - FINAL Denied 1) MAINTAIN WORKING SPACE AT A/C DISCONNECT
2) SEAL ENTRANCESABOVE CURRENT CARRING PARTS
3) GROUNDING TO BE A LISTED SYSTEM 690.41, 690.43 IF USING THE WEED MODULE CAUTIONS YOU NEED TO USE ALL THE PARTS OF THE LISTED SYSTEM
4) PLEASE PROVIDE INSTRUCTIONS FOR RACK MOUNTING AS INSTALLED PLANS SHOW DIFFERENT
5) INSTALL BOND JUMPER ON SERVICE MIPPLE 250.92
*MAIN BREAKER WAS CHANGED WITHOUT CLEARANCE