Permit: T12CM02474

Parcel: 110070110


Addresses:

4154 E GLENN ST

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
09/26/2012 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
08/03/2012 ELECTRIC - CONSTRUCTION POWER Partial Approval 1) THE TOP PLATE AT PLUMBING VENT- STRAPS ACROSS BOTH PLATES 8-16-DB MARKS BOTH SIDES
2) PROTECT PLUMB- BANG PLATES
3) CLEAN SURFACE 1312 AND GROUND BARS 250.12
4) NEED 1/4" HARDWARE RISER STRAP AND ROOF END INTO RAFTERS
5) NEED MECHANICAL PLANS ON SITE
07/11/2012 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/29/2012 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONNOT CONFIRM GROUNDING ELECTRODE SYSTEM
INSTALLED PER 250.50 & 250.64 NEC
VERIFY METER SOCKET DAMAGE DUE TO EVIDENCE OF HEAT