Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/29/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TABLE 250.122 30 OR 40 BREAKER GROUND #10 2) 6 X 6 J-BOX STILL MISSING GROUNDING/BONDING |
|
| 05/24/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/22/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND 6 X 6 J-BOX, EQUIP. GROUND 250 NEC 2) NEW FEEDER TO GUEST HOUSE TO HAVE EQUIP. GROUND PER 250.32 NEC 3) LOAD CONDUCTORS NOT TO EXIT TOP OF PANEL. SEE INFO ON INSIDE PANEL COVER (TOP) THIS AREA IS ISOLATED FOR SUPPLY CONDUCTORS ONLY 110.3 NEC |
|
| 05/04/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |