Permit: T12CM02412

Parcel: 138230260


Addresses:

665 W CALLE SEVILLA

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/05/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/29/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TABLE 250.122 30 OR 40 BREAKER GROUND #10
2) 6 X 6 J-BOX STILL MISSING GROUNDING/BONDING
05/24/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/22/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND 6 X 6 J-BOX, EQUIP. GROUND 250 NEC
2) NEW FEEDER TO GUEST HOUSE TO HAVE EQUIP. GROUND PER 250.32 NEC
3) LOAD CONDUCTORS NOT TO EXIT TOP OF PANEL. SEE INFO ON INSIDE PANEL COVER (TOP) THIS AREA IS ISOLATED FOR SUPPLY CONDUCTORS ONLY 110.3 NEC
05/04/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*