Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 05/03/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 2774 N. FAIR OAKS: 1) SMOKE DETECTOR MISSING IN HALLWAY 2) SMOKE DETECTORS IN BEDROOMS NEED BATTERIES 3) RECEPT FOR STOVE NOT SECURED TO WALL 2772 N. FAIR OAKS: 1) WIRE CEILING FAN IN LIVING ROOM TO CODE OR REMOVE. CANNOT HAVE CORD AND PLUG 2) PROVIDE SMOKE DETECTORS IN BEDROOMS AND HALLWAYS BOTH UNITS: 1) PROVIDE GLOBES OVER LIGHT BULBS IN CLOSETS 2) ALL WIRING EXPOSED TO SUNLIGHT ON NORTH AND EAST SIDE OF BLDG, MUST BE IN CONDUIT OR REMOVED 3) YOU CANNOT USE THE MAIN BREAKERS TO POWER CLOTHES DRYERS 4) IMPROPER WIRING METHODS AT FLOOR LIGHT IN CARPORT 5) ALL ROMEX CONNECTED INTO A BOX MUST HAVE THE PROPER CONNECTOR 6) ALL WIRE SPLICES MUST BE IN A BOX 7) CORDS ARE CONNECTED TO EVAP COOLERS WITHOUT FITTINGS 8) PROVIDE A QUALIFIED ELECTRICIAN TO DO THIS WORK 9) LIST MAY NOT BE COMPLETE |