Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/30/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE GROUND ROD SYSTEM 2) BOND GAS AND WATER LINES 3) RAISED LEETERS ADDRESS 4) DBL LUGGED NEUTRAL AND GROUND WIRES 1 PER LUG 5) 30 AMP WHITE LEAD RED OR BLACK 6) ALL EXTERIOR CONDUIT TO HAVE WEATHERED FITTINGS 7) DRIP LEG WATER HEATER 8) 3 SCREWS EACH FITTING ? 9" TPA B-VENT AND SECURE PER CODE |