Permit: T12CM02375

Parcel: 138233920


Addresses:

803 W OAHU LN

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/27/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/30/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE GROUND ROD SYSTEM
2) BOND GAS AND WATER LINES
3) RAISED LEETERS ADDRESS
4) DBL LUGGED NEUTRAL AND GROUND WIRES 1 PER LUG
5) 30 AMP WHITE LEAD RED OR BLACK
6) ALL EXTERIOR CONDUIT TO HAVE WEATHERED FITTINGS
7) DRIP LEG WATER HEATER
8) 3 SCREWS EACH FITTING ? 9" TPA B-VENT AND SECURE PER CODE