Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/12/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROPERLY INSTALL RED ICING WASHERS 110.3(B) 2. MAINTAIN WORKING SPACE IN FRONT OF INVERTER 110.26 3. NEED LABEL 690.17 4. LOOSE FITTINGS 5. TIE UP + SUPPORT MODULE DISCONNECTS AT ROOF JUNCTION BOX |