Inspection History Details
Inspection Status: Not Applicable
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2012 | ELECTRIC - RECONNECT | Not Applicable | IVRS - Inspection :* | |
| 06/05/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SECONDARY RISER CLAMP 2) NO BREAKERS IN PANEL TO BE HIGHER THAN 6-9 3) PROVIDE WATER TO GAS BONDS |
|
| 05/02/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FRONT LIGHT FIXTURE NOT WIRED TO CODE 2) SERVICE HAS NOT BEEN MAINTAINED IN GOOD WORKING CONDITION. MANY ADDED CIRCUITS CAUSING OVER LOAD TO EXISTING 30 AMP SERVICE. UPGRADE REQUIRED 3) EXPOSED WIRING INTERIOR THROUGHOUT 4) GROUNDED OUTLETS ON NON GROUNDED CIRCUIT THROUGHOUT 5) SMOKE ALARM BEDROOMS AND HALLWAY 6) TERMITE DAMAGE TO GARAGE ENTRY BEAM COULD DEEM STRUCTUALLY DANGEROUS |