Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 05/15/2012 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* | |
| 05/01/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SMOKE DETECTORS REQUIRED IN BEDROOMS 2) RECOMMEND GFI PROTECTED RECEPT OVER KITCHEN COUNTER SINK 3) LABEL MAIN BREAKERS AT SERVICE WITH ADDRESS AND UNIT NUMBER 4) GROUND ELECTRODE CONDUCTOR MISSING AT SERVICE EQUIPMENT |