Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/16/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) ON FINAL TO SEE BONDING TO WATER AND GAS FROM SUB PANEL AND CHECK NEUTRAL TO MAKE SURE IT IS NOT BONDED |
|
| 05/14/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHERE IS YOUR GROUNDING ELECTRODE SYSTEM? 2. WHERE IS PAPER WORK? 3. WHO IS PULLING IN SERVICE WIRES YOU OR TEP? |