Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2012 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |