Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) NEED LISTED MAST BRACE KIT 2) RISER HARDWARE TO BE 1/4" MINIMUM 3) SEAL ENCLOSURE ENTRANCE ABOVE CURRENT CARRING PARTS 4) DRYWALL SCREWS NOT APPROVED HARDWARE 5) VERIFY WATER AND GAS BONDS |