Permit: T12CM02184

Parcel: 133372590

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
08/14/2012 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
08/09/2012 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOND SERVICE RISERS AND NIPPLES 250.92 AND 250.102
2) PREVENT OBJECTIONABLE CURRENT- PARREL PATH
3) FILL UNUSED PORTION OF OPENINGS WITH NON COMBUSTABLE PRODUCT
4) NEED REJECTION PINS AND FUSES
5) LUGS LISTED FOR SINGLE CONDUCTOR ONLY IN CT CAN
6) LABEL SERVICE AND DISCONNECTS
7) PLEASE HAVE ELECTRICIAN OPEN GUTTER FOR INSPECTION
07/31/2012 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*