Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2012 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 08/09/2012 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND SERVICE RISERS AND NIPPLES 250.92 AND 250.102 2) PREVENT OBJECTIONABLE CURRENT- PARREL PATH 3) FILL UNUSED PORTION OF OPENINGS WITH NON COMBUSTABLE PRODUCT 4) NEED REJECTION PINS AND FUSES 5) LUGS LISTED FOR SINGLE CONDUCTOR ONLY IN CT CAN 6) LABEL SERVICE AND DISCONNECTS 7) PLEASE HAVE ELECTRICIAN OPEN GUTTER FOR INSPECTION |
|
| 07/31/2012 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* |