Permit: T12CM02141

Parcel: 141312370

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T12CM02141

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2012 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
06/26/2012 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECT FLEX DUCT SUPPORTS
INSULATION OF FLEX DUCT AT AHC UNIT CONN
SUPPORT DRYER VENT W APPROVED DUCT STRAP AT EACH AND OR WITH SOLID SUPPORT
CORRECT COLLAPSED EXHAUST FAN AT LAUNDRY
06/25/2012 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SECURE ALL WIRING CLOSE TO BOXES, CAN LIGHTS ALSO
LOW VOLTAGE - NO TAPE
CORRECT DUCT STRAPPING
PROVIDE MID STORY SUPPORTS AS REQUIRED DWV
PROVIDE LISTED PIPE CLAMPS ON ALL PIPE. SECURE OR DOUBLE UP ON TALONS
SUPPORT LINE SET ABV COILING
INSTALL PVC AS REQ PER CODE AND INSTALLATION STANDERDS
SEE HANDAT PRAISES???
TERMINATE ALL STRANDS OF ELECTRICAL CONDUTORS
PROTECT COPPER FROM STUCCO