Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 04/20/2012 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* 1) WE STILL HAVE GROUNDED RECEPTS ON NON GROUNDED CIRCUITS 2) TIGHTEN LOOSE FITTINGS |
|
| 04/18/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RESUPPORT XONDUIT & GROUND WIRE TO STRUCTURES 2) BACK OUTSIDE LIGHT FALLING OFF WALL 3) SMOKE DETECTORS REQUIRED IN HALLWAY & BERDROOMS - 6"-12" BELOW CEILING - 3' AWAY FROM COOLER VENT. 4) CHECK OUT MIX MATCH RECEPTACLES SOME GROUNDED SOME NOT. ALSO RECOMMEN GFI PROTECTED RECEPTS AT KITCHEN COUNTER 5) DISCONNECT SMALL UNIT IN BACK OR BRING UP TO CODE |