Permit: T12CM02000

Parcel: 140191110


Addresses:

748 E OREGON ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T12CM02000

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
08/07/2012 ELECTRIC - RECONNECT Denied SMOKE DETECTORS MUST BE BETWEEN 6'-12" BELOW CEILING TO DETECT SMOKE PROPERLY.
07/24/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
ITEMS NUMBERS 4, 2, 1, 3, 6, 7, 8
ONLY 2 OF 9 ITEMS CORRECTED DATED 6-28-12
A RE-FEE IS BEING ATTACHED TO THIS PERMIT
06/28/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL TITE FROM PANEL INTO GARAGE NOT TO CODE
2) PVC CONDUIT AT EXTERIOR NOT PROPERLY SUPPORTED
3) DOOR AT ELEC PANEL BREAKEN OFF
4) BARE WIRES HANGING OUT OF WALL IN LAUNDRY ROOM, PROVIDE APPROVED SWITCH COVERS IN LAUNDRY ROOM, TAPE NOT ACCEPTABLE
5) BARE WIRES HANGING OUT OF WALL ON REAR PORCH
6) EXTERIOR OUTLET COVERS BROKEN
7) SMOKE ALARMS REQUIRED IN BEDROOMS
8) BARE WIRES IN FURNACE ROOM
9) BARE WIRES HANGING OUT OF WALLLS AND CIELING IN GARAGE