Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/06/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2ND BRACKET ON RISER 2) FILL OPEN KNOCKOUTS IN DEAD FRONT 3) ADDRESS ON PANEL 4) BOND GAS LINE ON HOUSE SIDE OF METER KIT COUNTER OUTLETS REQUIRE 2 SEPERATE 20 AMP CIRCUITS |