Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/13/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/04/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH #3, 4 & 5 OF INSPECTIONS DATED 4/20/12
05/10/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/20/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED SERVICE CONDUCTORS
2) DERATE CONDUCTORS FROM NEW JUNCTION BOX 310.15
3) NEED CONNECTOR FOR GROUNDS
4) CHANGE OLD PANEL TO NEW JUNCTION BOX
5) STRAP GROUNDS TO BLDG
6) OK GROUND RODS AND BONDS