Inspection History: FIRE - FINAL
Permit Number - T12CM01718
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2012 | FIRE - FINAL | Approved | IVRS - Inspection :* GATES IN PATIO JUST OPEN AND CLOSE NO LATCHING WAS USE. PLACTIC EXIT SIGNS POSTED ON WALLS BY EXIT GATES. According to contractor owner is looking into installing panic hardware on gates on a later date. |
|
09/17/2012 | FIRE - FINAL | Denied | 1. Exit signs posted at gates in patio 2. Keep gates opening freely with spring closer and no latch, if you want to secure gates closed (locked) will need to install panic hardware only if any other unapproved lock is installed on gates a citation will be issued. 3. Address numbers (15") shall be posted on building front high above front door, hand out given. 4. Exit door out of kitchen shall have panic hardware or door knob only can not have both on door. 5. Call after seating is all built in patio area need to keep clear aisles (36")to all gates. 6. Stop changing seating layout from what approved plans show. |
|
07/30/2012 | FIRE - FINAL | Not ready for Inspection | 1. Work still needs to be done to patio. |