Permit: T12CM01700

Parcel: 11207437A

Inspection Status: Denied

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T12CM01700

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Denied

Date Description Inspector Results Comments
06/22/2012 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/01/2012 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 1/2" ID GAS FLEX NOT ADEQUATE FOR 210,000 BTU
2) PROVIDE 3/4" GAS PIPE AND DO NOT REDUCE TO 1/2" AT THE CONNECTION TO UNIT
3) NEED TO SEE THE DUCT SMOKE DETECTOR WITH AUDIBLE AND VISIBLE ALARM
4) COVER CANVAS CONNECTOR ON NORTH SIDE OF 7.5 TON UNIT
5) UNITS ARE ACTUALLY AT 2578 N. COUNTRY CLUB. 2525 IS BILLING ADDRESS