Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/10/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A GROUNDING ELECTRODE SYSTEM 2) PROVIDE SUPPORT ON MAST WITHIN 3' OF CONNECTION TO PANEL 3) PANEL IS MOUNTED TO HIGH. MAX HEIGHT TO TOP OF HIGHEST POSSIBLE OVER CURRENT DEVICE CANNOT EXCEED 6' 7" 4) PROVIDE A LADDER TO CHECK JUNCTION BOX ABOVE THE PANEL |