Permit: T12CM01685

Parcel: 135052850

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/27/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
04/10/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A GROUNDING ELECTRODE SYSTEM
2) PROVIDE SUPPORT ON MAST WITHIN 3' OF CONNECTION TO PANEL
3) PANEL IS MOUNTED TO HIGH. MAX HEIGHT TO TOP OF HIGHEST POSSIBLE OVER CURRENT DEVICE CANNOT EXCEED 6' 7"
4) PROVIDE A LADDER TO CHECK JUNCTION BOX ABOVE THE PANEL