Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 04/06/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEW DISCONNECT SWITCH TO BE PER 404.8 2) IDENTIFY THE GROUNDED CONDUCTOR 3) INSTALL MAIN BONDING SCREW 250.24 4) SERVICE NIPPLE TO BE 250.92 5) ONLY ONE CONDUCTOR PER TERMINAL LUG 110.14 |