Permit: T12CM01640

Parcel: 123111470


Addresses:

1439 E LINDEN ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T12CM01640

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
04/06/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NEW DISCONNECT SWITCH TO BE PER 404.8
2) IDENTIFY THE GROUNDED CONDUCTOR
3) INSTALL MAIN BONDING SCREW 250.24
4) SERVICE NIPPLE TO BE 250.92
5) ONLY ONE CONDUCTOR PER TERMINAL LUG 110.14