Permit: T12CM01628

Parcel: 110071370


Addresses:

2609 N FAIR OAKS AV


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T12CM01628

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
04/19/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
04/17/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) HIGHEST AVAILABLE BREAKER NOT OVER 6'7"
2) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH AN APPROVED DEVICE
3)INSTALL ALL STANDS UNDER LUGS & TIGHTEN
4) NEED TO SUPPORT RISER BELOW ROOFLINE & WITH LISTED MAST BRACK KIT ABOVE
5) PLEASE PROVIDE ACCESS TO JUNCTION BOX

INTERIOR OK