Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/25/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE APPROVED STRAPS FOR MC CABLE, NOT 16D NAILS 2) SUPPORT MC ABOVE CEILING WITHIN 12" OF TERMINATION AND 6' INTERVALS, ALSO LV CABLING TO BE SUPPORTED TO STRUCTURE PER 725-800 NEC 3) SOME AREAS COVERED (DRYWALL) PRIOR TO APPROVALS 4) COPYS OF PREVIOUS INSPECTION REPORTS TO BE ON SITE |
|
| 04/24/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING OUTLETS PER PLAN 2) UNCOVER ALL NEW OUTLETS FOR INSPECTION 3) CHECK ALL SIEZMIC WIRING |