Permit: T12CM01621

Parcel: 140160120

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T12CM01621

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2012 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/25/2012 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE APPROVED STRAPS FOR MC CABLE, NOT 16D NAILS
2) SUPPORT MC ABOVE CEILING WITHIN 12" OF TERMINATION AND 6' INTERVALS, ALSO LV CABLING TO BE SUPPORTED TO STRUCTURE PER 725-800 NEC
3) SOME AREAS COVERED (DRYWALL) PRIOR TO APPROVALS
4) COPYS OF PREVIOUS INSPECTION REPORTS TO BE ON SITE
04/24/2012 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING OUTLETS PER PLAN
2) UNCOVER ALL NEW OUTLETS FOR INSPECTION
3) CHECK ALL SIEZMIC WIRING