Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 04/06/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2 GROUND RODS 6' MIN APART, WATER/GAS PIPE BONDING 2) SUPPORT #4 BARE, 240V DRYER RECEPT 3) GROUNDS AND NEUTRALS TIED TOGETHER IN 6 X 6 J-BOX. SEAL HOLE BEHIND BOX, USE NON COMBUSTIBLE SEALANT 4) SUPPORT RISER CONDUIT WITHIN 3' OF TERMINATION. ALSO RISER CONDUIT DOES NOT APPEAR TO BE SCREWED IN TO HUB. ALSO HUB SCREWS NOT SEATED 5) RISER CONDUIT SHOULD ALLOW ROOF CLEARANCE PER 230 NEC AND UTILITY CLEARANCE FOR POOL 22' FROM WATER LINE PER NEC 680 6) CONSULT WITH TEP ALSO, MAY HAVE TO MOVE SERVICE OUT OF PORCH |