Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2012 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 04/30/2012 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMBUSTION AIR NEEDED FOR UTILITY ROOM 2) PLAN SHOWS SOLAR STORAGE TANK; REGULAR DOMESTIC WATER HEATER BEING USED REQUIRES PLAN REVISION OR 4 INLET STORAGE TANK PER PLAN 3) SECURE JOINTS OF VENT CONNECTORS TO CODE WITH 3 SCREWS PER JOINT 4) REMOVE T-HANDLE OR CAP OFF DRAIN BIB 5) INSTALL FLASHING FOR COPPER LINES PER PRODUCT LISTING 6) MAINTAIN DISTANCE BETWEEN FLASHINGS THRU ROOF OR SUPPLY MAINTENCE FREE CONNECTION BETWEEN FLASHINGS |