Permit: T12CM01602

Parcel: 136291230

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/29/2012 PLUMBING - FINAL Approved IVRS - Inspection :*
04/30/2012 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMBUSTION AIR NEEDED FOR UTILITY ROOM
2) PLAN SHOWS SOLAR STORAGE TANK; REGULAR DOMESTIC WATER HEATER BEING USED REQUIRES PLAN REVISION OR 4 INLET STORAGE TANK PER PLAN
3) SECURE JOINTS OF VENT CONNECTORS TO CODE WITH 3 SCREWS PER JOINT
4) REMOVE T-HANDLE OR CAP OFF DRAIN BIB
5) INSTALL FLASHING FOR COPPER LINES PER PRODUCT LISTING
6) MAINTAIN DISTANCE BETWEEN FLASHINGS THRU ROOF OR SUPPLY MAINTENCE FREE CONNECTION BETWEEN FLASHINGS